Transformer manufacturing workshop

Pad-mounted
Transformers

Compact outdoor distribution
with enclosed cable connections.

Transformer manufacturing workshop

ZGS pad-mounted
transformers

150, 500 and 1,000 kVA configurations for three-phase distribution. Series photographs illustrate enclosure designs; each technical panel identifies the electrical configuration.

150kVA

ZGS 150 kVA

Three-phase · 150 kVA

150 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.

500kVA

ZGS 500 kVA

Three-phase · 500 kVA

500 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.

1,000kVA

ZGS 1,000 kVA

Three-phase · 1,000 kVA

1,000 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.

ZGS series and electrical scope

Integrated outdoor distribution

ZGS transformers combine the transformer active part, an HV load-switch and fuse arrangement, and an LV connection compartment in a compact pad-mounted unit. The three-phase series serves above-ground distribution points for residential communities, commercial sites and industrial facilities.

Available configurations

The ZGS family covers 50–2,500 kVA at series level. The electrical tables on this page describe separate 150 kVA, 500 kVA and 1,000 kVA designs at 13.8 kV / 208 V. Enclosure photographs show series examples; voltage ratio, winding connection and electrical values belong to the selected configuration.

ZGS series scopeZGS
PropertySeries scope
Series capacity range50–2,500 kVA
Transformer typeThree-phase, oil-immersed, pad-mounted
CoolingONAN — Oil Natural Air Natural
Active partCopper windings and silicon-steel core
InstallationOutdoor, above-ground cabinet on a prepared foundation

The series range is distinct from the three 13.8 kV configurations detailed below. It is not a complete rated model schedule.

ZGS model designation

The ZGS designation identifies a combined, common-tank, three-phase transformer. The following fields specify the rated capacity and the high- and low-voltage winding ratings.

In the 1,000 kVA configuration sheet, ZGS-1000-13.8/0.208 identifies the rated capacity and 13.8 kV / 208 V windings. The connection group, frequency and accessory arrangement complete the electrical and mechanical specification. A model label should be read together with its matching rated data.

Reading the ZGS designation
Code or fieldMeaning
ZCombined type
GCommon-tank enclosure
SThree-phase
CapacityRated apparent power in kVA
HV / LVRated high- and low-voltage winding voltages

Tank and connection compartments

The transformer core and windings operate in an oil-filled tank. Oil provides electrical insulation and transfers heat to the tank and cooling surfaces, where natural airflow removes it. ONAN operation uses this natural circulation arrangement without a forced-air fan system.

The cabinet houses the HV switching and connection arrangement together with the LV distribution interface. For the 13.8 kV configurations, the listed enclosure protection is IP54 and the construction uses copper windings and a silicon-steel core. The tank, cabinet doors and cable openings each have a role in the complete outdoor enclosure.

The front doors provide access to the connection area while the tank and external cooling surfaces sit behind it. Compartment access, cable-entry openings and terminal positions should be coordinated as one assembly. The front and open-door photographs illustrate this physical arrangement.

Open Loop Feed cabinet with two sets of three primary phase connections

Loop Feed

Two sets of primary connections for incoming and outgoing feeder cables.

Open Radial Feed cabinet with one set of three primary phase connections

Radial Feed

One set of primary connections for an incoming feeder cable.

Integrated construction
PartFunction and construction
Transformer active partCopper windings and silicon-steel core immersed in insulating oil
Oil tankContains the active part and insulating/cooling oil
HV arrangementLoad switch and fuse with the incoming cable interface
LV compartmentOutgoing low-voltage connections and distribution interface
Cooling arrangementONAN: natural oil circulation and natural airflow
Outdoor enclosureIP54 specified for the three 13.8 kV configurations

Feed arrangement & connection interfaces

Radial and loop-feed arrangements

Incoming and through feeders

Radial feed and loop feed are available within the pad-mounted configuration. A radial arrangement terminates an incoming feeder at the transformer. A loop-feed arrangement provides incoming and outgoing HV cable positions so the transformer can form part of a feeder route.

Network operation

The feed arrangement determines the cable-compartment layout and the switching scheme. A loop-capable enclosure does not by itself define how the utility operates the network: loop-feed equipment can also be installed on a radial system. Source selection and sectionalizing functions depend on the actual switches and single-line diagram.

Single-line arrangement

Specify the incoming feeder, outgoing feeder where applicable, normal operating connection and required isolation points in the single-line diagram. These details establish the required cable positions and switch functions before terminal and protection components are selected.

  • Radial feed: the incoming HV circuit, transformer protection and LV supply are arranged around a terminating feeder.
  • Loop feed: incoming and outgoing cable positions are coordinated with the through-feeder and transformer switching arrangement.
  • Cable routing: cable entry positions, bend space and operating access follow the selected cabinet and termination layout.

HV switching and fuse protection

Switching and fusing

The integrated HV arrangement includes a load switch and fuse protection. Switching establishes the operating connection of the transformer or feeder, while fusing forms part of the overcurrent-protection arrangement. These functions have to work with the upstream network protection and the downstream LV protective devices.

Protection coordination

The single-line diagram brings the feed type, transformer connection and protection arrangement together. Switch function, fuse rating and cable termination are individual design selections; the kVA rating alone does not define them. Their coordination also depends on the available fault level and the operating requirements of the utility or facility.

Accessory specification

The accessory schedule should name the selected switch and fuse arrangement together with the required ratings and connection interfaces. This keeps the physical compartment layout aligned with the protection study and the operating procedure for the installation.

Protection and switching coordination
Engineering itemRelationship to the pad-mounted unit
HV load switchOperating connection for the selected radial or loop-feed arrangement
Fuse protectionTransformer protection coordinated with the supply and LV protection
Primary cable terminationVoltage class and interface matched to the HV connection arrangement
LV protective devicesCoordination with transformer output, circuit demand and system fault level

Cable, neutral and earthing interfaces

Primary and secondary connections

The HV and LV cable interfaces are arranged at the transformer compartments. The 13.8 kV configurations use a delta primary, so their winding connection is different from a grounded-wye primary design. On the secondary side, the star-point neutral supports the stated 208 V three-phase and 120 V phase-to-neutral supply.

Connection drawing

Cable entry, terminal layout and the neutral connection are carried into the connection drawing. This drawing links the incoming MV feeder, outgoing LV circuits and earthing connections to the actual cabinet arrangement. Cable size, termination type and the number of parallel LV conductors affect the space required inside the compartments.

Cable and terminal space

Identify the primary cable construction and termination interface, the outgoing phase and neutral conductors, and any required parallel cable runs before the terminal layout is finalized. The dimensions of the cable openings and the working space then follow the actual connections and approved installation drawing.

  • HV cable entry and termination positions for the chosen feed arrangement.
  • LV phase and neutral terminals corresponding to the selected winding connection.
  • Earthing connection points for the tank, cabinet and site earthing system.
  • Cable-entry openings and working space coordinated with the foundation and underground cable route.

Rated data & installation

13.8 kV input and 208/120 V output

Voltage and frequency

The three configurations use a delta-connected 13.8 kV primary and a star-connected 208 V secondary with an accessible neutral. The Dyn11 connection supports three-phase 208 V loads and 120 V phase-to-neutral service. The rated frequency is 60 Hz, with a separately selected 50 Hz design option.

Materials and rating data

Copper windings, a silicon-steel core and ONAN cooling are common to these configurations. Short-circuit impedance differs by capacity and forms part of the system fault-current and protection study. The detailed panels also include insulation levels, enclosure protection and the specified ambient-temperature range for each configuration.

Three-phase and neutral supply

The neutral is the star point of the low-voltage winding. A phase-to-neutral 120 V circuit is part of this three-phase secondary arrangement; it does not turn the transformer into a single-phase model. The load schedule and neutral requirements should accompany the single-line diagram.

13.8 kV / 208 V configuration data
Rated capacityRated HVRated LVFrequencyVector group
150 kVA13.8 kV, delta208 V line-to-line / 120 V line-to-neutral60 Hz; separate 50 Hz optionDyn11
500 kVA13.8 kV, delta208 V line-to-line / 120 V line-to-neutral60 Hz; separate 50 Hz optionDyn11
1,000 kVA13.8 kV, delta208 V line-to-line / 120 V line-to-neutral60 Hz; separate 50 Hz optionDyn11

These are separate copper-wound, Dyn11 configurations. The 50 Hz option is a design choice; it does not change a 60 Hz nameplate rating in service.

Product images illustrate ZGS enclosure arrangements. They do not identify the exact voltage or winding configuration in this table.

Insulation, impedance and losses

Insulation levels

The three 13.8 kV configuration sheets specify 34 kV power-frequency withstand on the high-voltage side and a 95 kV basic impulse level. The project insulation schedule should coordinate the transformer, primary cable interface and protective devices around the selected voltage and network arrangement.

Impedance and excitation

Short-circuit impedance is 4.5% for the 150 kVA and 500 kVA configurations and 5.75% for the 1,000 kVA configuration. The respective no-load-current limits are 0.8%, 0.7% and 0.6%. Keep these values with their capacity, voltage ratio and Dyn11 connection when carrying out the network study.

Reference losses

Each technical panel also includes approximate loss data from its configuration sheet, with load loss referenced to 75 °C. These values support preliminary specification. The final loss guarantees, test conditions and acceptance documents are agreed for the ordered design; the 50 Hz option needs its own rated data.

Impedance and excitation-current values
Rated capacityShort-circuit impedanceNo-load current
150 kVA4.5%≤0.8%
500 kVA4.5%≤0.7%
1000 kVA5.75%≤0.6%

Values apply to the 13.8 kV, Dyn11 configurations. They are not transferred to other voltage or winding arrangements.

Insulation levels in the 13.8 kV configuration sheets
Electrical propertySpecified value
HV power-frequency withstand34 kV
Basic impulse level95 kV

Configuration-sheet values; the required tests and acceptance documentation follow the project specification.

Cooling and outdoor enclosure

Cooling and outdoor enclosure
500 kVA ZGS tank and radiator example. Photograph shows the enclosure arrangement.

ONAN cooling uses the natural circulation of insulating oil and surrounding air. Heat passes from the core and windings to the oil, then through the tank and cooling surfaces to the environment. The listed configurations do not require a forced-air fan system.

The three 13.8 kV technical sheets specify an ambient range of −40 °C to +40 °C and an IP54 outdoor enclosure. Cooling surfaces need airflow, and the siting design should account for nearby walls, equipment and vegetation. Any different ambient or elevation conditions belong in the project specification.

Enclosure requirements include the cabinet construction, exposed surfaces and cable entries. The listed IEEE C57.12.28 reference addresses pad-mounted enclosure integrity; it does not establish the transformer’s electrical rating or approve a different site environment. The required finish and acceptance documents follow the selected enclosure specification.

Outdoor duty for the listed 13.8 kV configurations
ItemSpecification or project input
CoolingONAN — natural oil circulation and natural airflow
Ambient temperature−40 °C to +40 °C in the configuration sheets
Enclosure protectionIP54 in the configuration sheets
Airflow and accessSpace around cooling surfaces and access to operating compartments
ExposureDust, coastal salt and corrosive conditions stated with the project requirements

IP54 is an enclosure-protection specification, not a statement of suitability for immersion or flooding.

Foundation and installation interfaces

Foundation and installation interfaces
500 kVA ZGS cabinet example. Project dimensions and foundation details follow the approved drawing.

A prepared foundation supports the transformer and aligns its cable openings with the site cable route. The layout also leaves space for doors, cable terminations and operating access.

Earthing connects the enclosure to the site earthing system; neutral grounding follows the network design. The selected unit’s overall drawing defines its footprint, lifting points and mass, while the project design establishes anchoring and clearances.

Locate the transformer so that the cable route, door swing and operating approach remain usable after surrounding works are complete. Confirm handling access before delivery and use the approved lifting and foundation information for the ordered assembly.

Installation interfaces
InterfaceDesign purpose
Foundation and anchoringSupport the unit and align its base with the cable route
HV and LV cable openingsMatch the connection drawing and cable installation space
Tank and cabinet earthingIntegrate exposed metalwork with the site earthing system
Operating accessKeep doors, switching positions and terminations accessible
Lifting and handlingUse the unit-specific drawing, lifting points and mass

Clearances, anchoring and earthing details follow the project design and the local utility requirements.

Applications

ZGS transformers serve outdoor distribution points where the transformer and connection compartments need to occupy one compact location. Residential and commercial installations use the unit to connect a medium-voltage feeder to local low-voltage distribution. Industrial installations use the same arrangement to supply factory or plant loads.

Illustrative residential service verge with a closed green pad-mounted transformer and unobstructed access space

Residential communities

Place enclosed distribution equipment along the community service network, with underground cable entry and a clear maintenance area around the cabinet.

Illustrative commercial-campus service area with a closed pad-mounted cabinet and clear paved access apron

Commercial developments

Coordinate the transformer position with building loads, service roads and landscaped areas. Cabinet access remains separate from routine pedestrian and vehicle movement.

Illustrative industrial service lane with an enclosed green pad-mounted transformer beside a factory building

Industrial facilities

Locate distribution equipment near plant loads while allowing room for cable routing, cabinet access and maintenance vehicles. The site layout defines the required protective measures.

Illustrative application environments.

The 208 V / 120 V configurations are relevant when those voltages match the load schedule. A 13.8 kV primary, Dyn11 winding connection and the selected feed arrangement must also match the supply network. Capacity selection follows the connected load, operating demand and the project load plan.

  • Residential communities: a compact outdoor transformation point for local LV distribution.
  • Shopping and service facilities: supply to three-phase and phase-to-neutral circuits at the required secondary voltage.
  • Factories and industrial zones: outdoor distribution near the plant load, with cable routing and protection integrated into the site design.
  • Utility distribution: above-ground equipment connected into the selected radial or loop-feed arrangement.

Pad-mounted transformer procurement FAQs

The site design brings the distribution duty, enclosure location and cable route together. Confirm the utility supply voltage and feed arrangement first, then match the secondary circuits and neutral requirement to the selected transformer configuration.

For an outdoor installation, provide the ambient-temperature range, elevation and exposure conditions. The layout should leave room for cooling airflow, door operation, cable work and equipment handling, with drainage and foundation details coordinated with the civil design.

Which supply-network details are required?

Supply network

Primary voltage, radial or loop feed and the single-line diagram

Design reviewWinding ratio, cable positions and switching arrangement

How should the secondary load be described?

Secondary load

Three-phase demand, phase-to-neutral circuits and expected load growth

Design reviewCapacity, 208/120 V supply and neutral interface

Which ambient and exposure conditions matter?

Ambient and exposure

Temperature range, elevation, dust, coastal salt and corrosive conditions

Design reviewCooling, insulation surfaces and enclosure finish

What foundation and drainage inputs are needed?

Foundation and drainage

Pad location, cable openings, anchoring and site drainage

Design reviewBase arrangement and civil interface

What information defines the cable space?

Cable access

Cable sizes, termination type, bend space and parallel LV conductors

Design reviewCompartment layout and connection drawing

How should operating and handling access be planned?

Operating access

Door swing, approach space, lifting route and maintenance access

Design reviewOverall layout and approved installation drawing

Which technical documents should accompany the order?

Technical documents

The product-information panels contain the electrical and construction data for the 150 kVA, 500 kVA and 1,000 kVA configurations. For project procurement, the rated data sheet, single-line diagram and connection drawing should describe the same voltage ratio, vector group, cooling arrangement and feed type.

ZGS Pad-mounted Transformer — 150 kVA150 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.
ZGS Pad-mounted Transformer — 500 kVA500 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.
ZGS Pad-mounted Transformer — 1,000 kVA1,000 kVA ZGS enclosure views and a separate 13.8 kV / 208 V, Dyn11 configuration with ONAN cooling.

Document scope and configuration notes

The final technical package also defines the cabinet arrangement, overall dimensions, terminal positions, protection components and inspection requirements. Electrical ratings, enclosure requirements and acceptance tests are separate parts of that package. Loss guarantees and physical dimensions belong to the selected design and its order documents.

Engineering documents for the selected configuration
DocumentInformation to align
Rated data sheetCapacity, voltage ratio, frequency, vector group, cooling and loss conditions
Single-line diagramRadial or loop feed, switch function and fuse/protection coordination
Connection drawingPrimary interfaces, LV phase and neutral terminals, and earthing points
Overall and foundation drawingDimensions, cable openings, anchoring, mass and lifting points
Inspection and test packageOrdered model, acceptance requirements and applicable document scope

Use the project drawings for the selected electrical variant when planning installation and cable termination.

  • Capacity, primary voltage, secondary voltage, frequency and winding connection.
  • Radial or loop feed, the single-line diagram and the required switching/protection arrangement.
  • HV and LV cable details, terminal arrangement, neutral and earthing requirements.
  • Installation environment, quantity, destination and project drawing or testing requirements.

Pad-mounted Transformer Technical Guides

View all resources